The heat to take out of the space for an IT load.
cooling load kW = IT MW × 1,000 × (1 + other heat % ÷ 100)
tons of refrigeration = cooling load kW ÷ 3.517
The calculator has not started: it needs JavaScript. The formula above is all it does.
Nearly all the power IT equipment draws leaves it as heat. The cooling plant's own power adds to what is finally rejected outdoors, and sizing the plant is mechanical design.
A screening estimate from the figures you typed. It is not an engineering study, a utility commitment or advice on a transaction.